              防爆空調電動機繞組間短路故障

               

               

              購買防爆空調流程

              • 1、聯系在線客服或撥打0577-62884866,62994866咨詢產品信息
              • 2、議定型號,數量,付款方式(匯款、代收)、運輸及售后服務
              • 3、傳真方式簽訂購銷合同
              • 4、雙方按合同約定履行責任和義務
               

              防爆空調電動機繞組間短路故障
                    在電源電壓、起動繼電器等電氣控制部件都正常的悄況下,起動繼電器連續過載,熱保護繼電器觸點跳開,壓縮機不轉動用萬用表檢查時,發現起動繞絢阻估比正常值明顯城少,這說明故障是由壓縮機電動機起動繞組短路造成的,
                    壓縮機電動機姒強起動和運行,但運行電流比正常值(一般為1.1~I.2A)大一倍以上;響聲明顯比原來大;運行幾分鐘后,熱保護繼電器觸點跳開,用萬用表檢查時,發現運行繞組的阻值比止常值小幾歐,這是電動機運行繞組匝間短路造成的故障。
                    防爆空調通電后熔絲連續熔斷用萬用表檢查時,發現電動機運行或起動繞組與封閉機殼之間發生短路,即阻值很小或阻值為0 (在正常情況下,封閉機殼三個接線柱弓封閉機殼之間的阻值應在5MΩ以上) 。

               